Paper title: CALCUL DE L`INDUCTANCE SHUNT POUR LA RÉDUCTION DE LA SURTENSION LE LONG DE LIGNE LONGUE À VIDE: CAS GÉNÉRAL (CALCULATION OF SHUNT INDUCTANCE FOR OVERVOLTAGE PROTECTION ALONG NOLOAD LONG TRANSMISSION LINES: GENERAL CASE)

Author(s): ABDELHAFID BAYADI,

Abstract:

Dans le problème de transport de l'énergie électrique une ligne de transmission à longue distance a une capacité très élevée de transfert de puissance si la tension le long de la ligne est effectivement contrôlée et maintenue à sa valeur nominale. Dans ce travail l’auteur présente une méthode de calcul générale pour un nombre quelconque des inductances de différentes puissances et installées à des positions quelconques le long de la ligne. L'approche proposée est mise en évidence par des calculs numériques portant sur une ligne de 1200 km de longueur et en considérant deux problèmes généraux (détermination de la distribution de la tension le long de la ligne en donnant à l’avance les puissances et les positions des inductances shunt et choix de la puissance des inductances dont leurs positions sont déjà déterminées pour une distribution de tension donné d’avance). Les résultats obtenus selon cette approche montrent qu'une distribution de tension est maintenue, en tout point de la ligne, conforme aux exigences internationales relatives à la variation de la tension pour les réseaux très haute tension et sont en parfait concordance avec des résultats de simulation en utilisant le logiciel "Alternative transients program (ATP) version of the Electromagnetic Transients Program (EMTP)". (In the problem of transporting electrical energy a long-distance transmission line has a very high power transfer capacity if the voltage along the line is effectively controlled and maintained at its nominal value. In this work the author presents a general method of calculation for any number of inductors of different reactive power and installed at any position along the line. The proposed approach is evidenced by numerical calculations on a 1200 km long line and considering two general problems (determining the voltage distribution along the line by giving in advance the powers and positions of the shunt inductors and calculating the power of the inductors whose positions are already determined for a voltage distribution given in advance). The results obtained according to this approach show that a voltage distribution is maintained, at every point of the line, in accordance with the international requirements relating to the variation of the voltage for very high voltage networks and are in perfect concordance with simulation results using ATP-EMTP software.)

Keywords: Protection contre les surtensions, Inductance shunt, Réseaux très haute tension, Compensation de la puissance réactive, Simulation, Alternative transients program (ATP) - version of the electromagnetic transients program (EMTP). (Overvoltage protection, Shunt inductance, High voltage networks, Reactive power compensation, Simulation, ATP-EMTP.)

Year: 2019 | Tome: 64 | Issue: 2 | Pp.: 107-112